Furnace
Goodman Furnace error codes
86 codes across 6 model families. Start with your model number, because Goodman reuses the same numbers for different faults on different boards.
Goodman shares code tables with other brands
Goodman, Amana and Daikin furnaces run on shared control platforms, so they share code tables. The same number can mean different things on different Goodman model families.
Find your model family
The model number is on the data plate, usually on the side or back of the unit or behind the service panel. It usually starts with the letters or numbers in the name below.
| Code | What it means | How urgent |
|---|---|---|
| E0 | Lockout after too many ignition retries | Critical |
| E1 | Low stage pressure switch stuck closed at start of heat | High |
| E2 | Low stage pressure switch stuck open | Critical |
| E3 | Open high limit switch | High |
| E4 | Flame detected when no flame should be present | Critical |
| E5 | Open low voltage fuse | High |
| E6 | Low flame signal | High |
| E7 | Igniter fault or improper grounding | High |
| E8 | High stage pressure switch stuck closed at start of heat | High |
| E9 | High stage pressure switch stuck open | High |
| EA | Reversed 115 volt polarity | High |
| EC | Inducer motor overcurrent fault | High |
| EF | Auxiliary input open | Low |
| Ed | Rollout switch open | Critical |
| b0 | Blower motor not running | High |
| b1 | Blower communication error | High |
| b2 | Blower horsepower mismatch | High |
| b3 | Blower motor running in power, temperature or speed limit | High |
| b4 | Blower motor current trip or lost rotor | High |
| b5 | Blower motor locked rotor | High |
| b6 | Blower motor voltage or over temperature trip | High |
| b7 | Incomplete parameters sent to motor | High |
| b9 | Low indoor airflow | High |
| d0 | Data not yet on network | Moderate |
| d4 | Invalid memory card data | High |
| IF | Internal control fault | High |
Similar to GMVM96 but has no rollout code, which changes the safety story.
| Code | What it means | How urgent |
|---|---|---|
| E0 | Lockout after too many ignition retries | Critical |
| E1 | Low stage pressure switch stuck closed | High |
| E2 | Low stage pressure switch stuck open | Critical |
| E3 | Open high limit switch | High |
| E4 | Flame detected when no flame should be present | Critical |
| E5 | Open low voltage fuse | High |
| E6 | Low flame signal | High |
| E7 | Igniter fault or improper grounding | High |
| E8 | High stage pressure switch stuck closed | High |
| E9 | High stage pressure switch stuck open | High |
| EA | Reversed 115 volt polarity | High |
| b0 | Blower motor not running | High |
| b1 | Blower communication error | High |
| b2 | Blower horsepower mismatch | High |
| b3 | Blower running in a protection limit | High |
| b4 | Blower current trip or lost rotor | High |
| b5 | Blower motor locked rotor | High |
| b6 | Blower voltage or over temperature trip | High |
| b7 | Incomplete parameters sent to motor | High |
| b9 | Low indoor airflow | High |
| d0 | Data not yet on network | Moderate |
| d4 | Invalid memory card data | High |
| IF | Internal control fault | High |
On this platform F01 to F09 are blower speed setup values in the installer menu, not faults. IdL means Idle, not 1DL.
| Code | What it means | How urgent |
|---|---|---|
| IdL | Idle | Normal |
| FAn | Fan command | Normal |
| gH | Gas heat demand | Normal |
| dFt | Defrost demand | Normal |
| F01 | Blower speed setup value 1 | Normal |
| EE0 | Lockout after repeated ignition failures | Critical |
| EAF | Flame signal out of range during a heat cycle | Critical |
| E1I | Ignition fault | Critical |
| EbL | Blower fault, lower circuit | High |
| EbU | Blower fault, upper circuit | High |
| EAL | Airflow fault, lower limit | High |
One LED counter is shared between the gas section and the cooling section, so furnace and AC codes cannot be separated.
| Code | What it means | How urgent |
|---|---|---|
| 1 flash | Ignition failure, rollout open, or auxiliary limit open | Critical |
| 2 flashes | Open end centrifugal switch | High |
| 3 flashes | Closed end centrifugal switch with no combustion motor | High |
| 4 flashes | Open high limit switch | High |
| 5 flashes | Flame detected when no flame should be present | Critical |
| 6 flashes | Compressor time delay or short cycle timer | Moderate |
| 7 flashes | Limit opened five times in the same call for heat | High |
| 8 flashes | Indoor or outdoor thermostat open, cooling only | Low |
| 9 flashes | Heat pump or loss of charge switch open, cooling only | High |
GMV / GMH / GMS / GMN
Goodman, Amana and Daikin legacy furnace flash codes (GMV, GMH, GMS, GMN series)
1980s-2000s · 9 codes
One shared control table covers the whole legacy group, so these series are listed together. Not every series reports every code: the GMN, GMP and GMT group stops at 5 flashes, the GDS, GHS, GMS and GKS group stops at 7, and only the two-stage GMV reports 9. Each code page states which series it applies to.
| Code | What it means | How urgent |
|---|---|---|
| 1 flash | Lockout after too many ignition tries | Critical |
| 2 flashes | Pressure switch stuck closed | High |
| 3 flashes | Pressure switch stuck open | Critical |
| 4 flashes | High limit switch open | High |
| 5 flashes | Flame detected when no flame should be present | Critical |
| 6 flashes | Rollout switch open | Critical |
| 7 flashes | Low flame signal | High |
| 8 flashes | Igniter fault or bad grounding | High |
| 9 flashes | High stage pressure switch stuck open | High |
A Honeywell-platform control with its own wording and its own code assignments. It is not the GMV table.
| Code | What it means | How urgent |
|---|---|---|
| 1 flash | Furnace lockout after 3 ignition retries | Critical |
| 2 flashes | Pressure switch circuit closed | High |
| 3 flashes | Pressure switch circuit not closed | Critical |
| 4 flashes | Primary or auxiliary limit circuit open | High |
| 5 flashes | Flame sensed with no call for heat | Critical |
| 6 flashes | Rollout limit open or control module fuse blown | Critical |
| 7 flashes | Flame sense signal low | High |
| 8 flashes | Problem with igniter circuit | High |
Common questions
- How many Goodman furnace error codes are documented here?
- 86 codes across 6 model families. Every code page lists what the fault means, the causes, the checks you can safely do yourself, and when it stops being worth resetting the unit.
- How do I read the code on a Goodman furnace?
- It depends which board you have. Some Goodman furnace families print the code as text, and others blink an LED that you count against a legend printed on the board. Check the table above, because the two are read in completely different ways.
- Which Goodman furnace model do I have?
- The model number is on the data plate, usually on the side or back of the unit or behind the service panel. The families on this page are GMVM96, GMVC95, GM9S96, APG13, GMV / GMH / GMS / GMN, GMSS9 / GCSS9. The model number starts with the letters or numbers in that name, which is the only reliable way to pick the right code table.
- Do other brands share Goodman furnace codes?
- Goodman, Amana and Daikin furnaces run on shared control platforms, so they share code tables. The same number can mean different things on different Goodman model families.