Mitsubishi Electric MSZ / MSY / MUZ / MUY GL NA series error code 4 blinks, 2.5 s OFF
Overcurrent, or compressor startup failure
Which models this applies to. This page covers the Mitsubishi Electric MR SLIM GL series split codes.
What is specific to the MSZ / MSY / MUZ / MUY GL NA series platform
MSZ and MSY indoor units with MUZ cooling only and MUY heating outdoor units on R410A. There is no numeric display: you count blinks of the upper operation indicator lamp on the indoor unit. The same blink count can mean an indoor fault or an outdoor one, and a three second steady hold before the blinking with no beep is what tells the two apart, with a second LED inside the outdoor unit narrowing several outdoor codes to one part.
Your control board does not print the code. It blinks an LED, and you count the flashes against a legend printed on the board or inside the access panel. Count a full cycle before you read it, because the pattern pauses and repeats.
Quick answer
On Mitsubishi Electric MSZ / MSY / MUZ / MUY GL NA series, 4 blinks, 2.5 s OFF is a fault. It means overcurrent, or compressor startup failure. A first thing to check: A supply voltage that is too low, which makes the compressor draw excessive current.
- Applies to
- Mitsubishi Electric MSZ / MSY / MUZ / MUY GL NA series
- Mitsubishi Electric MR SLIM GL series split codes · Mini Split
- Type of code
- Fault
- Urgency: Needs attention soon
- First safe check
- Read the inverter LED: eleven blinks is overcurrent, twelve is the startup failure. That single number separates the two.
What 4 blinks, 2.5 s OFF means on this model
An outdoor fault, split by the inverter LED. Eleven LED blinks is a large current flowing into the power module on the smaller models or the IGBT module on the GL24. Twelve LED blinks is a compressor synchronous abnormality, which the manual also calls the compressor startup failure protection, where the compressor current waveform is distorted.
Symptoms you will notice
- Upper lamp blinks four times after a three second hold, no beep
- The system will not start, or starts and drops out
- The system may restart after a delay and trip again
- The compressor does not establish a steady hum
Common causes
The code tells you what the control detected, not which part failed. These are the causes we see most often, roughly in order of likelihood:
- A supply voltage that is too low, which makes the compressor draw excessive current
- A supply voltage that is too high or unstable
- A hard to start or failing compressor
- A compressor connector that is loose or not seated
- A failed power module or IGBT module
- A closed stop valve forcing the compressor against a restriction
What you can safely check
These are homeowner-level checks. None of them need you to open a live electrical compartment or work on gas.
- Read the inverter LED: eleven blinks is overcurrent, twelve is the startup failure. That single number separates the two.
- Measure the supply voltage at the outdoor unit under load. A supply that looks fine at no load is the classic cause of both of these.
- Reconnect the compressor connector and check the stop valve, in the order the manual gives.
Do not do these
- ×Do not keep restarting. Both of these are drive protections and repeated attempts damage the drive section as well as the compressor.
- ×Do not replace the compressor and the inverter board together without proving which failed, which is an expensive way to fix one fault.
- ×Do not install heavier fusing to stop the protection operating.
When to call a technician
Book a technician, do not keep resetting it
This fault will not clear on its own. Every power cycle gives the control one more failed attempt, and repeated attempts are what turn a cheap part replacement into a seized or contaminated system.
- The refrigerant circuit is sealed and legally requires licensed handling. Opening it without certification releases refrigerant and can put the whole system in violation of regulation, so a low-pressure or high-pressure fault on this equipment is a call-out, not a weekend job.
- If the appliance has stopped mid-cycle, is making a noise you have not heard before, or smells burnt, stop reading here and call. Those are symptoms of something the fault code does not describe well enough.
A licensed technician job. Supply voltage under load is not a homeowner measurement.
What it costs to fix
Parts
Compressor $1,400 to $3,000. Inverter P.C. board $500 to $1,200. Power or IGBT module $200 to $600.
Labor
Three to six hours depending on whether the cause is electrical or mechanical.
DIY or technician
A licensed technician job. Supply voltage under load is not a homeowner measurement.
Typical US part and labor ranges, 2026. They vary by region, model and contractor, so treat them as a planning figure, not a quote.
Scope of this code
- Code table
- Mitsubishi Electric MR SLIM GL series split codes
- How this model reports the code
- Blinking LED, counted against a legend
- Models in scope
- Mitsubishi Electric MSZ / MSY / MUZ / MUY GL NA series
- How this platform differs
- MSZ and MSY indoor units with MUZ cooling only and MUY heating outdoor units on R410A. There is no numeric display: you count blinks of the upper operation indicator lamp on the indoor unit. The same blink count can mean an indoor fault or an outdoor one, and a three second steady hold before the blinking with no beep is what tells the two apart, with a second LED inside the outdoor unit narrowing several outdoor codes to one part.
- Checked
- Confirm on your own unit
- Find the model number on the data plate, then check this code in the service manual for that model. Manufacturers revise code tables between model years, and a revised board can renumber a fault.